Napco Security (Gemini Commercial) GEM-P1664 - Up to 64 user codes Security Control Panel in Large H401 Enclosure w/ Transformer, Lock and Key.
The GEM-P1664 Hybrid 8 to 64-Zone Control/Communicator features 8 zones expandable to 64 zones with multiplexing and supports all standard Gemini RP and K-Series Keypads, plus new Gemini DK-Series Door-Style Keypads and new VPS Series talking multifunction keypads, as well as reliable, NAPCO Gemini crystal-control transmitters and receivers, too.
Supporting up to 64 user codes and 16 relays, the GEM-P1664 control features easy menu drivenSelf-Programming Plus keypad programming (for all zones), which includes new alpha keypad question-prompts, even for setting test timer, fire zones and exit/entry and follower zones.
Additionally, the panel can be remote up/downloaded using easy-to-use NAPCO Quickloader Software.
Features:
- 8 hybrid zones on-board including two 2-wire fire zones in large, locking enclosure (12.5" x 14" x 3.75")
- With multiplexing, can accommodate up to 64 EOL zones (from alpha keypads or multiplex modules, including the low-cost GEM-EZM4/8 Expansion Module).
- Programmable partitioning for 4 areas
- Up to 64 users codes
- Up to 4 areas
- Uses all the standard Gemini crystal-control wireless
- Uses all the standard Gemini keypads, new DK-Series door-style keypads and multifunction VPS Series talking keypads (shown above)
- Two money-saving paks with custom alpha door keypad GEMP1664DK1PK; or with multifunction GEMK1VPS keypad with built-in talking voice, PIR and UL siren, GEMP1664VPSPK
- Backup/double/split reporting; three 20-digit telephone numbers
- Dynamic battery test
- Reports alarms, restores and troubles by zone.
Specifications:
- Input Power: 16.5-18.0 VAC via Class 2 Plug-In 20VA, 40VA or 50VA Transformer
- Loop Current: 3mA; 5mA for 2-wire smoke-detector zones
- Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke detector zones
- Alarm Voltage Output: 1; Programmable Negative Outputs: 2
- Auxiliary Power Output: 11.7-12.5 VDC
- Remote Power Output: 12 VDC regulated
- Combined Standby Current - See WI1501